Multi-line 2 CGC 400 Application Software series 1.x.

您即将下载 Multi-line 2 CGC 400 Application Software series 1.x.

您已选择下载我们的软件。

几秒钟内,您将收到一封包含下载链接的电子邮件。

如果使用软件有问题,请联系support@deif.cn.

诚挚的祝福,

DEIF A/S

本软件受DEIF A/S版权保护。请点击上述链接可查阅DEIF A/S版权和许可协议(EULA)。

本软件适用于以下DEIF产品

您即将下载 1.15.1

与上一版本相比,主要更新如下:

Corrections:

  •    Invalid SPN messages are no longer shown in the DM1 log. TSC1 SA is now configurable for the Perkins protocol.
版本号 发布日期 描述

1-15-2

29/06/2020

Version 1.15.2 based on version 1.15.1

Corrections:

  •    The MB will no longer trip on startup if the breaker is configured as a normally closed relay and the mains is okay.

1.15.1

26/02/2020

Corrections:

  •    Invalid SPN messages are no longer shown in the DM1 log. TSC1 SA is now configurable for the Perkins protocol.

1.15.0

24/01/2019

New features:

  • Support for LCD module based on the NT7538 display controller.

1.14.1

04/01/2018

Changes:

  • Improved precision of display readout of total energy counter.
  • Added new view line for absolute running hour counter with minutes.

Corrections:

  • Multi-input HW limit erroneous warning at power on.
  • EIC measurement alarms are now inhibited during EIC communication failure.

 

1.14.0

15/08/2017

Version 1.14.0 based on version 1.13.1

New features:

  • Phase sequence error is now detected and handled at both sides of the breakers (common alarm extended to two separate alarms in menu 2150).

Changes:

  • Phase sequence error is no longer detected when the voltage or frequency is outside volt./ frequency ok values.

Corrections:

  • Support of checksum in TSC1 telegram added for Volvo Penta EMS 2. Merge from SIPC 0497.
  • Phase sequence error status texts could appear even if they should be inhibited. GB would not close because of phase sequence error even if it was inhibited.

 

1.13.1

19/05/2016

Corrections:

  • Initiated cool-down cannot be aborted when a wire break fail class alarm is present.
  • Running hours offset is now stored and handled correct.
  • Scania EMS2 KWP2000 log clearing now possible.
  • Inhibit evaluation added to a number of AC alarms.
  • Genset data (e.g. oil pressure) was not displayed/updated correctly in the USW.
  • Negative values in range -1.0 to 0.0 showed correctly in the display.
  • Corrected "Limits relay" handling when setting up alarm output.
  • A problem with downloading new language from the USW has been corrected. The Language download returned “burn error”.

1.13.0

24/02/2015

Changes:

  • Scaling range 1 kV - 75 kV changed to 0.4 kV - 75 kV.

Corrections:

  • Attempting to stop during idle at start would ramp the engine to full speed and keep running, if the running detection speed had been reached during idle run
    Running hours counter not saved, and total energy counter not shown correctly in display
  • Space padding in master texts has been removed. Further when writing translations, space padding is removed from each text programmed 

1.12.0

27/11/2014

New features:

  • MTU ADEC CANopen engine communication interface now supports shutdown override.

Changes:

  • Mains voltage failure limit changed from 80-100 % to 40-100 %

Corrections:

  • Inverse Time Overcurrent protection aligned with IEC 60255 part 151 (AGC 200)
  • MTU MDEC 302/303 protocols battery voltage measurement corrected.
  • Regarding Idle start timer: Timer now resets if the Start Off timer is running.
  • AMF sequence was incorrect in some cases.
  • Start enable has to be energised to activate the regulation.
  • Option H5/H7, MTU alarm "AL Speed Demand Failure" no longer present all the time.
  • The reactive power was wrong when the phase rotation was L1L3L2.
  • Unit could reboot if a Modbus command was sent while 'Inhibit modbus commands' was active

1.10.0

08/04/2014

Changes:

  • Language translation changed. From now on it is not possible to select a different font.
  • The two fonts are now merged, containing all previously used characters.
  • The new font contains some new characters. If any unsupported signs are written to the device the signs will appear as ' ' (space). USW 3.37.0 or higher required.

Corrections:

  • Several menu texts were not using translations - Corrected.
  • Parameter outputs A and B could not be configured as "Limits" - Corrected.
  • Option C2 inverse over-current malfunctions when using "Customer" defined curve - Corrected.
  • The Fuel Pump Logic feature now disabled under power up while measurements are invalid.
  • Relay setting error could occur each time the unit starts up - Corrected

1.01.0

26/11/2013

New features:

  • RPM based on calculation from the AC reading

Corrections:

  • Pre-configuration of RMI 6-8 corrected

在此页面,您可以下载产品的更新软件,并使用各种实用工具和附加组件设置、检测故障和配置产品。

请注意,用户无法更新我们的所有产品。同时也不是所有产品都配有实用工具。因此,本页的软件列表不能视为DEIF产品的概述。

DEIF将登记您注册的下载邮箱地址,以便在未来需要时发送有关的更新信息。

DEIF不对产品更新失败或使用实用工具造成的任何后果负责。DEIF A/S也不对软件升级导致的产品行为变化的后果负责。用户始终有责任在调试前确保正确的设置和配置。请在更新产品之前查阅软件的更新日志。

www.deif.cn软件下载许可协议

下载的软件仍是DEIF的财产。本软件不得用于商业目的分发, 不得全部或部分更改或重复使用,也不得出售给任何第三方。

最新版本,功能齐全

我们始终建议您安装最新版本的软件,以充分利用您的DEIF产品。

所有更新的软件都可以从www.deif.cn->支持->下载->软件栏目下下载。

如果您在查找产品的相关软件时有任何疑问或问题,请随时致电丹控电气(上海)有限公司,电话: +86 21 68796200,或者发送电子邮件至support@deif.cn, 我们随时为您服务。