Multi-line 2 GC-1F Application Software series 2.x.

您即将下载 Multi-line 2 GC-1F Application Software series 2.x.

您已选择下载我们的软件。

几秒钟内,您将收到一封包含下载链接的电子邮件。

如果使用软件有问题,请联系support@deif.cn.

诚挚的祝福,

DEIF A/S

本软件受DEIF A/S版权保护。请点击上述链接可查阅DEIF A/S版权和许可协议(EULA)。

本软件适用于以下DEIF产品

您即将下载 2.33.0

与上一版本相比,主要更新如下:

New features:

  • Five M-Logic alarms have been added.
  • In the AMF variant the inhibits "Genset Hz/V NOT OK" and "Mains Hz/V NOT OK" have been introduced. In the ATS variant the inhibits "Source 1 Hz/V NOT OK" and "Source 2 Hz/V NOT OK" have been introduced.

Changes:

  • Timers have been removed from #2240 and #2250. The alarms are now instant.
  • Sleep mode can no longer be disabled.
  • The sleep mode timer will now start running even though an unacknowledged alarm is present. Furthermore the alarm LED is no longer turned off when sleep mode is active.

Corrections:

  • While an ATS was powered down and a source went bad, the ATS would not go to a healthy source when it powered back up in auto. This correction only affects ATS controllers with pulse breakers.
  • The controller no longer tries to reclose the breaker when an active alarm is configured with Trip MB or Trip GB fail classes.
  • The ATS now considers a breaker, tripped by a fail class, the same as a mains failure, and will change source if healthy.
  • Extended stop timer is now activated if running feedback disappears abruptly.

 

版本号 发布日期 描述

2.33.0

16/03/2017

New features:

  • Five M-Logic alarms have been added.
  • In the AMF variant the inhibits "Genset Hz/V NOT OK" and "Mains Hz/V NOT OK" have been introduced. In the ATS variant the inhibits "Source 1 Hz/V NOT OK" and "Source 2 Hz/V NOT OK" have been introduced.

Changes:

  • Timers have been removed from #2240 and #2250. The alarms are now instant.
  • Sleep mode can no longer be disabled.
  • The sleep mode timer will now start running even though an unacknowledged alarm is present. Furthermore the alarm LED is no longer turned off when sleep mode is active.

Corrections:

  • While an ATS was powered down and a source went bad, the ATS would not go to a healthy source when it powered back up in auto. This correction only affects ATS controllers with pulse breakers.
  • The controller no longer tries to reclose the breaker when an active alarm is configured with Trip MB or Trip GB fail classes.
  • The ATS now considers a breaker, tripped by a fail class, the same as a mains failure, and will change source if healthy.
  • Extended stop timer is now activated if running feedback disappears abruptly.

 

2.32.0

16/09/2016

New features:

  • Parameter #2240 and #2250 external trip alarm of GB/CB1 and MB/CB2 has been added.

Changes:

  • Sleep mode is now enabled by default. If any alarms are present, they have to be acknowledged for the display to turn off the backlight.

Corrections:

  • Breaker open feedback alarms removed two seconds when breaker open signal is given and the alarm is already acknowledged.
  • It is now possible to reset an external IO setup from the display of the GC-1F.
  • An ATS unit will no longer automatically open its breakers when in manual mode.
  • A GC-1F ATS configured with pulse breakers could issue an open pulse when powercycled. If pulse breakers and breaker feedback is configured, it will now maintain the breaker positions from before the power cycle.
     

2.31.1

19/12/2014

  • Support for HW revision 7 added.

2.31.0

02/10/2013

New features:

  • Added EIC support for priority 7 on diagnostic message 1 and 2.

Corrections:

  • Minimised the risk of communication error on the service port.
  • EIC coolant temp., oil temp. and charge air temp. scaling are corrected for MDEC 302 and MDEC 303 protocols. 
  • Incorrect M-Logic interpretation corrected.
  • EIC transmission rate of CAN telegrams is corrected for the Volvo Penta protocol.
  •  Day of week is automatically adjusted when the date is changed.

2.30.0

29/06/2012

  • Support of upcoming hardware (1.06) implemented.
  • EIC: MTU Smart Connect 'EIC faults' handled correct.
  • EIC: EIC idle speed also set if a digital input is configured as IdleSpeed and input is activated.

2.24.0

12/03/2012

  • Supply voltage showed correct if large changes (above 10V) occurres.
  • Relay 3 available as limit relay.
  • EIC: Receiving single DM1 diagnostic not restricted in content any longer for all J1939 protocols.
  • EIC: Occurrence counter available in DM1 and DM2 logs.
  • EIC: Scania EMS speed offset handling corrected.

2.22.0

19/05/2011

  • Breaker pulse feedback handling improved for handling flicker.
  • Selection of language from USW saved correctly in unit

2.23.0

12/05/2011

New features:

  • EIC: MTU J1939 Smart Connect supported (see documentation).
  • EIC: After treatment / Diesel Particular Filtering implemented.
  • EIC: Caterpillar (Perkins): Two DM1 logs available for support of ADEM (primary) and EMCP (secondary) at the same time.
  • EIC: Caterpillar (Perkins): Start/stop signal to ECU can be enabled/disabled via M-logic.
  • EIC: Speed control signal to ECU can be inhibited (enabled/disabled) via M-logic.
  • EIC: Inhibit of EIC alarms can be setup via M-logic.
  • EIC: Standard GC-1F/2 Idlerun functionality now turns the engine to 700rpm on different engines (see documentation).
  • EIC: Protection lamp status and Malfunction lamp status implemented on J1939.
  • EIC: Both priority 3 and 6 are supported for Dash Display PGN, DM1 and DM2 logs.
  • EIC: Cummins: Shutdown override signal available.
  • EIC: Coolant level alarms (2 levels) implemented in menu 7670+7680.

Changes:

  • EIC: Support of 19bit SPN numbers in DM1 and DM2 logs.
  • EIC: Engine hours available available up to 99000hours in display readout.
  • EIC: When changing nominal frequency, a ramp function will be performed.
  • EIC: Modbus readings of a few EIC data; Coolant temperature, Fuel temperature and Charge Air Temperature where presented with different number of decimals depending on the engine protocol selected. This has now been aligned so data is presented in the same manner independent of engine protocol selected.

Corrections:

  • External I/O: Recognition of modules during power up secured for general I/O variants e.g. Wago. Correct recognition could randomly fail.
  • External I/O: Actual number of digital inputs are handled correct for general I/O variants to prevent wrong status indications in USW Input/output window.

2.21.0

25/03/2011

  • Shutdown override inhibit flag respected, so only alarms with failclass shutdown and no inhibit, stops the engine during a shutdown override period.
  • Reset of fire pump (shutdown override) hour counter possible from USW.
  • Engine Interface Communication: Transmit rate of speed telegrams (FF46 and TSC1) to VolvoPenta EMS2 increased from 40ms interval to 20ms interval.
  • Engine Interface Communication: Speed ramp increase and decrease setting increased to ±1500rpm and nominal rpm setting is used as start up point.
  • Setup of Number of teeth available from the device.
  • Setup of Language available from the device.
  • Setup of CT secondary available from the device.
  • Setup of CT primary available from the device.

2.00.0

01/03/2011

Initial release

  • Compared with version 1.23.x you get:
  • Status OK relay on terminal 3-4 is now configurable.
  • Able to work down to -40°C via option L2. Option L2 is a display heater hardware.
  • Short circuit protection up to 350% current.
  • All three VDO’s have a 0-2500ohm range.
  • Backlight dimmer control via display or USW.
  • Auto Acknowledge on selected alarms.
  • Power up added to event log.
  • LED indication during download of firmware.

Extra's

  • Parameter files from version 1.2x.x can be reused in the 2.xx.x software.

2.20.0

28/02/2011

  • ATS mode implemented (generator-mains and source-source).
  • Various ATS switches supported (2COMH, 2COEH, 3COMH, 3COEC etc).
  • Remote breaker handling implemented.
  • Remote mode change implemented.
  • Parameter for startup mode implemented.
  • Auto-mode shift parameter implemented.
  • Generator / mains OK inputs implemented for ATS mode.
  • Bypass to generator / mains inputs implemented for ATS mode.
  • Mains ok / fail status outputs implemented.
  • Source 1 and source 2 start /stop outputs implemented for ATS mode.
  • Testmode indication in display.
  • Testmode timer adjustable from display.
  • Breaker status outputs implemented.
  • Operation mode outputs implemented.
  • Busbar over/under voltage protections implemented (2 levels).
  • Busbar over/under frequency protections implemented (2 levels).
  • Inhibit functionality added to several parameters.
  • Handling of setup with no breakers improved.
  • Idle mode via digital input improved for AUTO mode.
  • Phase sequence protection improved for pulse relays

2.10.0

03/01/2011

  • Off mode implemented. The gen-set is completely blocked when entered OFF mode.
  • Engine Interface Communication: Speed ramp increase and decrease via digital inputs implemented.
  • GB and MB pulse control implemented.
  • Q> (Q export) and -Q> (Q import) protections added.
  • Option M19 added. Relay 47 is normally closed in standard hardware, but normally open if option M19 is chosen.
  • Support of general External IO modules following CiA 401. This is the CANopen device profile for generic I/O modules. Beckhoff, WAGO, Schneider, and many other brands use this protocol and now supported by GC-1F.
  • Support of 11 languages.
  • Log: New entries in event log for test sequence start.
  • Inhibit functionality added to several parameters.
  • Enable/disable functionality added to several parameters.
  • VDO fuel user defined curve display readout range changed to follow the two most extreme points.
  • Extended timer range for Stop failure alarm.
  • Engine Interface Communication: New measurements available ADEC protocol.
  • GSM: Channel number added and Header info removed from SMS message send when alarms occurs.
  • Engine Interface Communication: Improved support of preheat for Volvo Penta EMS 2.
  • Engine Interface Communication: Improved support of IVECO engine status.
  • Handling of kWh counter reset improved: Unwanted reset during power cycle prevented.

2.00.1

03/01/2011

  • Multi inputs in mA (or configured unit) display range increased from ±10000 to ±32000
  • Cut off level for AC measurements improved.

在此页面,您可以下载产品的更新软件,并使用各种实用工具和附加组件设置、检测故障和配置产品。

请注意,用户无法更新我们的所有产品。同时也不是所有产品都配有实用工具。因此,本页的软件列表不能视为DEIF产品的概述。

DEIF将登记您注册的下载邮箱地址,以便在未来需要时发送有关的更新信息。

DEIF不对产品更新失败或使用实用工具造成的任何后果负责。DEIF A/S也不对软件升级导致的产品行为变化的后果负责。用户始终有责任在调试前确保正确的设置和配置。请在更新产品之前查阅软件的更新日志。

www.deif.cn软件下载许可协议

下载的软件仍是DEIF的财产。本软件不得用于商业目的分发, 不得全部或部分更改或重复使用,也不得出售给任何第三方。

最新版本,功能齐全

我们始终建议您安装最新版本的软件,以充分利用您的DEIF产品。

所有更新的软件都可以从www.deif.cn->支持->下载->软件栏目下下载。

如果您在查找产品的相关软件时有任何疑问或问题,请随时致电丹控电气(上海)有限公司,电话: +86 21 68796200,或者发送电子邮件至support@deif.cn, 我们随时为您服务。